PBS                The product was developed as a result of the implementation of the project no. PBS3 / A1 / 15/2015 entitled "Innovative chemicals with the use of modified imidazoline for the refining, oil production, metallurgical and machine industries"                   NCBiR             

General Information:

Pachem-CR-1021_T is an innovative, multi-functional corrosion -scale inhibitor- dispersant package used for water cooling installations in the refinery, mining and energy industries, which is based on phosphonates, polymers and copolymers as well as environmentally friendly corrosion inhibitors. Pachem-CR-1021_T prevents the formation and precipitation of inorganic salts, mainly calcium carbonates. It disperses precipitated carbonates. Prevents a  pitting, cavitation and crevice corrosion as well as deposit attack. It is effective in a wide range of  parameters for the circulating water parameters. It has low environmental impact. Does not contain inorganic phosphates. Does not contain carcinogenic compounds, i.e. nitrites, chromates, hydrazine. Stable in contact with oxidizing biocides.

Typical properties:

ParameterUnitValueTest method
Appearance at 20 0C  - colorless to yellow PB-01 - Edition No. 1
Density at 15 0C  kg/m3 1050-1150 PN-EN ISO 12185:2002
Pour point  0C < -10 PN-ISO 3016:2005
Flash point  0C  > 100 PN-EN ISO 2719:2007
Viscosity at  40 °C mm²/s < 5 PN-EN ISO 3104:2004
Solubility in hydrocarbons - very good Visual inspection
Water solubility - very good Visual inspection

Application:

Dosage of Pachem-CR-1021_T is recommended to ensure the durability of steel elements of heat exchangers, which life without adequate protection against corrosion and stone is 0.5 - 2 years. The use of Pachem-CR-1021_T will result in :
- extending the life of protected installations and devices
- limiting of repair and cleaning costs
- reduction of downtime during repair

Treat rate:

The multifunctional corrosion-scale inhibitor-dispersant Pachem-CR-1021_T package should be dosed continuously, in proportion to the amount of water supplied to the cooling system. It is recommended to keep the Pachem-CR-1021_T concentration at 50-250 ppm in the cooling system (recommended dose 100 ppm). There is not recommended the dosage above 250 ppm. The dosing level depends on the quality of refilling water and the quality of the water in the cooling system. The higher the general hardness and the carbonate hardness, the higher is the dosage.

Packaging:

Pachem-CR-1021_T is available in 200 liter drums or 1000 liter IBCs. Other packagings are available on request.

MSDS card (for registered clients only):

Attention: Properties and data provided above are for information purposes only. Detailed properties of the product and guaranteed levels of efficiency are given to our clients in Technical Data Sheets.